VISUBAT type III

Email: nhat.nguyen@vietinstrument.com
VISUBAT type III

INTERNAL IMPEDANCE MEASUREMENT

Storage battery monitor, without loss of function

 

Storage battery monitor, without loss of emergency function

Mô tả chi tiết

Reliability

The measuring current and the coupling circuit are controlled by microprocessor.

Security

Use without disconnection! the battery backup function is maintained. No electrolyte handling, weighing is replaced by electrical measurement.

Turning the device on or off as well as all communications functions are accessible to the user.

Forecast

Delivered with software under Windows® XP/2000/Vista/7, 8 10 v32&64 bits ensuring:

storage

visualization of measurements

database management.

Simplicity

Only two cables for coupling and a measuring probe to move to each element. The VISUBAT takes care of all the coupling and decoupling procedures from the battery.

CONCEPT of internal resistance of an (open) lead accumulator.

The capacity of an accumulator depends on three factors:

the density of the electrolyte the temperature

the mass of active material

These three factors influence the value of the internal resistance (electrical connection resistance).

This variation in resistance reflects a discharge or aging of the accumulator.

The VISUBAT can be used on both open-lead and sealed-lead batteries.

Presentation

  • Robust aluminum table case with handle
  • Dimensions: 410 x 302 x 158 mm
  • Mass: 8 kg .

Features

Food :

  • 230 Vac ± 10% 50/60 Hz + single-phase earth
  • Consumption 230 VA

 

Measures :

  • Impedance:

0.000 mΩ to 0.999 mΩ

1.00 mΩ to 9.99 mΩ

10.0 mΩ to 90.0 mΩ

Accuracy 2%

  • Element tension:

0.00 to 18.00 Vdc

Accuracy 1%

  • Overall battery voltage:

0.6 Vdc to 250.0 Vdc

Accuracy 1%

  • Temperature

0 to 45°C

  • External current by current clamp. To measure the current flowing in elements connected in parallel (option).

 

Memory Capacity:

  • 100 x 27 elements or 48 x 60 elements.
  • Memory retention of 10 years
  • During testing and return the device displays the time, operator name, battery code and cell number.

 

Protections:

  • General power supply by
  • Permanent monitoring of the circuit
  • Protection against reverse polarity.

 

Temperature Range :

  • Operating temperature: 0 to 40°C
  • Storage temperature: 0 to 50°

 

Main Functions Of The Software:

  • Creation of the park
  • Programming the measurement campaign in the device
  • Automatic reception and archiving of measurements
  • 2D/3D visualization of measurements: digital and graphic readings (evolution of the battery or element by element).
  • Alarm programming.
  • Edition of measurement reports.
  • A single file, in access® format, contains the entire database. THE
  • Compatible with all three generations of devices.
Zalo