VE 1200-N

Email: nhat.nguyen@vietinstrument.com
VE 1200-N

Primary current injection

 
2400

TO MAX

  • High current case up to 2400 A
  • Rated power available at output: 3.25 kVA
  • Maximum power available at output: 7.2 kVA
  • 1 high speed output available at 5V
  • Current adjustable from 0 to 2400A
  • Robust FLIGHT CASE design with casters
  • True RMS Current Measurement (TRMS)
  • Integrated multifunction stopwatch
  • Testing of current transformers: CT ratio and phase shift
  • Testing thermal or magnetic image circuit breakers
  • Bushing tests
Mô tả chi tiết

Presentation

  • Flight case type housing
  • Dimensions L x W x H: 570 x 310 x 510mm
  • Mass ≈ 52 kg
  • Equipped with castors with brake

Features

Grocery : 

230V 50/60Hz

 

Protections:

  • General power supply via circuit breaker
  • Injection by electronic control

 

Generators:

A single generator usable as a current generator with an output of 3 ratings: 1A, 15A, 2400 A.

The output current is adjustable up to

  • 650 A for 15 mins
  • 1200 A for 4 mins
  • 2000 A for 30 s
  • 2,400 A max

These data depend on the cable sections used, the contact resistances, and the heating of the generator of the case, moreover for correct operation of the assembly it is necessary to observe a rest time at least equal to the injection time.

Cables used: 2 x 2m with a section of 95mm2

 

Generator No-Load Voltage: 5.3 V

Maximum power available: 7.2 kVA/30s

Digital Measurement Module

The control module allows the recording of time, threshold and TC report measurements in a FLASH memory internal to the device. This data can be repatriated and consulted subsequently on a PC equipped with Windows®. Computer connections are provided by USB .

 

Internal ammeter:

  • 2 ranges 0-200 A and 200-2000 A with automatic switching
  • Accuracy: 1%

 

External ammeter:

  • 2 ranges 0-1A and 1-10A
  • Accuracy: 0.5%
  • The external ammeter is associated with a CT ratio and phase shift measurement function.
  • This allows you to determine the correct orientation of the CTs.

 

Stopwatch

  • internal on/off
  • external on/off
  • triggering on dry contact or AC/DC voltage 12 to 250 V
  • accuracy: 0.02% +-1ms
  • measuring range: 9999.999 s

 

Injection cables:

  • VE1200-CA-3M-ETRI 2 x 3m section 190 mm2 with brackets
  • Cables of different lengths, sections and connectors are available on request.
 

 